L06 - Advanced Calculations
1. Overview (KM)
Spectroradiometry
2. Photometry (PR)
Distribution photometry
Photometric Integrators
3. Calculation of Direct Component (PR)
Point sources
Linear sources
Regular areas sources
Irregular area sources
4. Calculation/prediction of reflected and inter-reflected component (GD)
Irregular and regular arrays of luminaires
Domed and coffered ceilings
5. Road lighting (PR)
Reflectance tables
Luminance calculations
Uniformity calculation
Small target visibility
6. Glare (GD)
Glare systems (TM10, CIE, UGR)
7. Field Measurement of Light (PR)
Illuminance and luminance measurement in the field
8. Design for seeing (KM)
Cubic illuminance
L06 (1). Measurement Techniques - Spectroradiometry
Overview (L&L pp. 67-8)
Spectroradiometry is the measurement and analysis of the spectral distributions
of lamp sources. The measurements are made using a spectroradiometer. This
consists of a monochromator, a photometer and some means of converting the
output readings into relative spectral power distributions
The function of the monochromator is to disperse the homogeneous
radiation from the light source into a spectrum with provision for isolating
discrete bands of energy with known bandwidth. The components of a monochromator
are
· Entrance
slit
· Collimating
device
· Dispersing
element – splits up incoming light into its spectral distribution
· Exit
slit
The monochromator scans over the spectrum produced by the dispersing element. A
typical monochromator has 0.05nm ± 0.2nm resolution, and can scan 22.5 nm/s. A common means of performing
spectral power distribution measurements is to take readings of the spectrum
at 5nm intervals with a instrument bandwidth of 5nm over the wavelength range
required. This is a compromise giving reasonable resolution over the spectrum
while keeping down the number of readings.
For accurate results, it is necessary to irradiate the optical system and
the photocell uniformly. This can be achieved by irradiating a pressed barium
sulphate plate (a nominally perfect diffuser), and mounting the plate so
that the entrance slot is uniformly irradiated. The detector is a silicon
photodiode with a known spectral response curve.
Diffraction Gratings
In the M300E monochromator the dispersing device is a diffraction grating. This
has the advantage over prisms of linear dispersion, but they suffer from
the problem of overlapping orders; however this can be overcome with filtering. In
addition, gratings are capable of better resolution of the spectra than are
prisms.
Light as wave and a particle
Light is electromagnetic radiation, and thus can be regarded as either a
wave of electromagnetic energy, or a stream of photons. The main
observations in support of light as a wave motion are interference and diffraction effects.
A diffraction grating consists of many narrow equally spaced lines ruled
onto glass or metal. Diffraction occurs at each slit and in the same direction
each slit creates a similar diffraction pattern.
Let d be the separation between two lines in the grating. Then wavelets
from two corresponding points P and Q on two adjacent slits
will have a path difference of d sin q. We
want to find out where interference between these two adjacent wavelets
will be constructive. These wavelets will superimpose if the path difference
is a multiple of the wavelength l of the incident light, i.e.

When n = 0, q =
0, and constructive interference appears in line with the incident
beam direction. This is known as the zeroth order fringe. It is
the brightest fringe.
For a given wavelength of light, l,
a bright fringe appears at an angle q where sin q =
nl/d i.e. the angle of
interference is proportion to the wavelength. If white light is incident
on the grating each colour will produce its maximum interference at a different
angle, and a spectrum will be formed. When n = 0, all wavelengths
form maxima at 0 degrees, and a white maxima will be formed.
When n = 1, the first order spectrum is
produced. All colours of light are produced with violet being deflected
least. By measuring the spectral power at different angular positions, we
can determine the relative spectral power of diffferent parts of the spectrum.
Higher order spectra can be produced, and they
tend to spread out the spectrum over a large angular range, allowing more
precise measurements to be produced. Unfortunately, these orders can overlap. Filters
can be used to overcome these overlapping orders.
Calibration
Calibration is carried out by taking measurements on a suitable lamp of
known spectral power distribution under the same conditions as the test lamp. The CL2
absolute spectral irradiance standard lamp is such a lamp. It has the
following properties,
· 12V
100W
· Grit
blasted
· Aged
at 8.3A for 150W (???)
· Tested
by a test house, who return the following properties
· Spectral
irradiance curve
· Chromaticity
co-ordinates
· Illuminance
at 0.5m
· Correlated
colour temperature
For each point in the spectrum the ratio of the measured current from the
detector for the test lamp and the calibrated source is multiplied by the
known spectral power distribution of the standard source. This gives the
spectral power distribution of the unknown lamp at this point.
The spectral power distribution is the first step in calculating a number
of important parameters of a lamp. The relative spectral power distribution
is suitable for calculating the chromaticity co-ordinates and the CIE colour
rendering index Ra.
Calculation of chromaticity co-ordinates
In order to calculate the chromaticity co-ordinates, we need to calculate
the tri-stimulus co-ordinates X, Y, Z. We obtain these from the spectral
power distribution fl using the following equations,

where

Integration limits include the whole visible spectrum. The chromaticity
co-ordinates can be calculated from
;
; 
where x + y + z =1.
L06 (2). Measurement Techniques – Photometry
Distribution photometry
General principles
The unit of intensity is the Candela and is one lumen per steradian. For
photometric data of luminaires, we usually work with candelas per thousand
lamp lumens. Intensity is measured indirectly – the photometer measures
illuminance, and the inverse square law is used to measure intensity, since
the distance is known (I = d 2 E). As photometry is dependant
on the the inverse square law, it is important that the length of the luminaire
is short relative to the path length to the cell (ratio of path length to
length of longest side should be greater than 1:5)
Goniophotometers
A goniophotometer is used to measure the intensity distribution of
a luminaire. It uses a photocell which has a spectral sensitivity which
corresponds to the V(l) curve. We
use calibrated lamps, which have been run for 100 hours to allow them time
to stabilize.
The specification for all the equipment used to photometer luminaires is
laid down in BS 5489 to ensure the accuracy of results. BS 5225 gives
details of measurement techniques for obtaining photometric data for luminaires,
including laboratory conditions, and procedures for simple luminance and
illuminance measures.
Whenever using photometric information the test reference number should
be noted. This allows tracking back to the original luminaire and test conditions
if a installed scheme fails to work properly.
BS 5225 lays down the following requirements for tolerances on goniophotometers,
· Axis
of rotation to the vertical – ±0.50
· Axis
of rotation of the arm moving the mirror system or photocell to the horizontal
– ±0.50
· The
two axes should intersect at the effective centre of the photocell – 10mm
· Angles
indicated correctly - ±0.50
· Electricity
supply
· Ample
current handling capability
· The
harmonic content should be below 3%
· To
hold voltage to better than values in requirement tables below
· Frequency
stability to be introduced by European legislation
· Air
temperature and movement
· Measured
to ±0.50
· The
air around the luminaire to be draught free
· Temperature
controlled to values in requirements table below
Requirements Table
|
Lamp type in luminaire
|
Filament Lamp
|
Fluorescent Lamp
|
Other Discharge
|
|
Voltage
|
Rated Volts ±0.2%
|
Rated Volts ±0.5%
|
Rated Volts ±0.5%
|
|
Temperature
|
250C ±50C
|
250C ±10C
|
250C ±20C
|
In summary, the characteristics required for the goniophotometer to produce
accurate results are,
· Minimize
stray light by light baffles
· Control
air temperature
· Avoid
errors due to
· Non-linear
photocell
· Voltage
fluctuations
· Mirror
sagging
· Mirror
reflectance
The goniophotometer maintains the luminaire in the desired attitude. You
measure in the position of luminaire use. To achieve the desired optical
path length, mirrors are often used; the path should be at least five times
the largest dimension of the light fitting. The mirrors should be optically
flat, and have a uniform surface finish.
Angular systems
Indoor and street lighting luminaires are generally measured in their normal
operating position and the co-ordinate system should take account of this
by having the reference point directly below the luminaire. The C-gamma
system of photometric angles is the most common and used for all interior
and most exterior ones too. The angle C represents the plane in azimuth,
and g represents the plane in elevation. The axis of the system passes
through the centre of the luminaire. g are
measured from the nadir.
There are two other angular systems B-Beta and A-Alpha. The B-beta system
is sometimes used for floodlights and road lanterns. The A-alpha system
is used for automobile headlights. Converting from one system to another
is a simple matter of geometry.
Floodlights, projectors, automobile headlights and all other concentrating
beams have to be tested at much greater distances than indoor luminaires. The
detector should be far enough away so that it ‘sees’ the whole of the reflector
flashed with light. For normal floodlighting, as used in stadium lighting,
33m is sufficient, but by international agreement automobile headlamps are
tested at 25m. One consequence of the long path length is that the photocell
has to be fixed, and the luminaire rotated.
Measurement of light
The illuminance meter used to measure light should meet BS 667 – Illuminance
meters, although cosine correction is not needed, since the cell is
always normal to the light source. It is important that the photopic response
of the cell is correct, since the luminaire may colour the light of the
lamp, changing its spectral distribution.
Calculation of flux from intensity
Intensity is flux per unit solid angle, so by multiplying intensity values
by the solid angles over which they are valid flux may be calculated. The
solid angle between two angles of elevation measured from the nadir, q1 and q2, is
. From
this it is easy to calculate the flux for each intensity value, and thus
the LOR of the luminaire.
If a sphere is divided up into a series of zones of solid equal angle then
the calculation of total flux becomes easier. Russell angles are
chosen so that they are in the centre of solid zones. The formula to calculate
the Russell angles is,

where n is the number of angles in the set and k is an integer
between 0 and N/2 –1.
Calibration of results
There are two methods of calibration,
· One
can scan the bare lamp on the goniophotometer, calculate its LOR and work
out a scale factor by which to multiply the results of the luminaire scan
· The
LOR of the luminaire may be measured in an integrator and then when the total
flux of the luminaire is calculated, a factor can be used to make the two
agree.
Photometric Integrators
An integrator is used to compare the flux of lamps and to measure the LORs
of luminaires.
Operating principles
The inner surface is finished in a matt white paint with a surface reflectance
factor of between 75% and 85%. The light from the source is bounced around
the sphere and is substantially evenly distributed over the surface. In
a sphere it can be shown that the indirect light reaching any point is independent
of the position of that point. Hence the inter-reflected illuminance is
constant over the whole surface.
Components of an integrator
· Integrator
should be spherical
· Possible
to use other shape, for example a cube
· If
a non-spherical shape is used, checks should be made to ensure uniform reflection
properties
· Sphere
diameter should be at least ten times the size of any compact lamps, 2 times
the length of linear lamps and 1.5 times the maximum dimension of any luminaire
used.
· Translucent
window should illuminate the photocell, and it should be flat to the edge
of the sphere.
· The
material of this window should has transmission properties which are independent
of the angle if incident light.
· The
cell should closely follow the spectral response of the CIE photopic curve,
in order to deal correctly with coloured light sources.
· A
screen is provided to stop light falling directly on the photocell head.
· Screen
size should be no bigger than needed
· Additional
screen provided above auxiliary lamp
· A
GLS is used as the auxilary lamp
· It
is used to assess the self-absorbtion properties of the test lamp.
· The
surface finish should be both uniform and achromatic
· Integrators
should be repainted regularly as dirt accumulates preferentially on the lower
surfaces.
Calculation of LOR for a luminaire

where
A – luminaire in and on; aux lamp off
B – luminaire in and off; aux lamp on
C – luminaire in and on; aux lamp off
D – luminaire in and off; aux lamp on
L06 (5). Road lighting
Lighting for different road classifications
Main roads
On main roads, the needs of the driver are most important. The task of
the driver is to locate obstructions in the road ahead. To do this the lighting
needs to be bright enough to make small objects with small contrast visible. Over
the range 0.5 cd/m2 to 2 cd/m2, it is estimated that
an increase in luminance of 1 cd/m2 leads to a 35% decrease in
road accidents.
Thus it is luminance that is important to the driver so main road lighting
is based on the calculation of luminance. Illuminance is not a good measure
of road lighting as the luminance pattern is dependent on the road surface
as well as the lighting. The brightness of the area surrounding the road
is also important; if it is too bright then it will raise the drivers adaptation
level, if it is too dark then it will be hard to see pedestrians off the
road who may be waiting to cross.
Minor roads
The lighting on minor roads is aimed much more at the needs of pedestrians. The
main objectives in lighting minor roads are
· Detection
of obstacles
· Facial
recognition
· Visual
orientation
· Comfort
For detection of obstacles by pedestrians it has been found that average
illuminances in the range 3 to 10 lux is needed with a minimum illuminance
value of 1 lux. Facial recognition is closely correlated with semi-cylindrical
illuminance. Whilst S-C illuminance is not used in the British Standard,
the levels of horizontal illuminance are such that in general requirements
for facial recognition are met.
Visual orientation implies the ability to read the names on the road signs
and the numbers on the houses. This aspect is not considered in the British
Standard although some engineers try to place lanterns so that the road signs
are illuminated.
Comfort is again largely controlled by the restriction of glare. As pedestrians
move more slowly through an area they do not suffer from disability glare
to the same extent. Discomfort glare may be a problem so the intensities
of lanterns near the horizontal must be limited and luminaires should not
be mounted at eye height.
Measures used in road lighting
Disability glare
Light scatter in the eye causes Disability Glare. This causes extra
light to fall on the image of the object. The veiling luminance reduces
the contrast that objects have against their background as it contributes
to both the object and background luminance; CEFF = LB/
LB + LV
Consider an object that is just visible in the absence of glare. When glare
is introduced it will no longer be visible. To make this object visible
again, it will be necessary to increase the contrast. The percentage by
which the contrast must be increased to make the object just visible is known
as the Threshold Increment (TI). The CIE has arrived at a standard
way to calculate the TI that is valid for luminances in the range 0.5 to
5.0 cd/m-2,

Visual comfort
Visual comfort is of course related to average illuminance. However it is
also related to the longitudinal uniformity of the lighting (UL),

Discomfort glare
This is due to high luminance sources in the visual field. In most installations
if the disability glare requirements are met, then there is no problem with
discomfort glare.
Overall uniformity
As the adaptation state of the driver’s vision is set by the average value
of the road luminance it is important that the darkest point on the road
is controlled or else objects in some parts of the road will not be visible. The
measure used to control the uniformity of road luminance is overall uniformity
(UO),

Surround ratio
Lighting the area either side of the road is important in allowing drivers
to see pedestrians and other road users who may be about to cross the road. The
lighting in a zone 5m either side of the road should be bright enough so
that pedestrians can be seen, but not so bright as to change the adaptation
state of the driver.
The surround ratio (SR) is defined as the ratio of the
average illuminance on a 5m strip adjacent to the road compared with the
average illuminance on road. Note that for motorways and other roads where
pedestrians are excluded it is not necessary to use the surround ratios.
Visual guidance
A row of street lanterns can provide useful visual cues to the path of the
road by day and night. Care should be taken in siting columns at junctions
and on bends so that a false impression of the road layout is not given. Indicators
such as changing from low to high pressure sodium at junctions as a visual
cue is also useful.
Characterization of road surfaces
It is common to characterize road surfaces by a number of parameters,
· The
bulk reflection factor q0
· The
specularity factor S1,

where r(0,2) is the reduced luminance co-efficient for b=0
and tan g =2 and r(0,2) is the reduced
luminance co-efficient for b=0 and tan g =2.
Road have categorizations, with the most common road type in the UK, asphalt,
being categorized C2.
Luminance calculation
The luminance of the road is given by
where
q is a function of a, b and g,
· a -
angle from eye to position of observation along road (typically 10)
· b -
angle from normal to road at position of measurement to observer
· g -
angle from lantern head to position of measurement
Road reflections are normally stored as R-tables where
. This
makes the luminance calculation much easier as the cos3 is embodied
within the table. The table is indexed by b and tan g (where
tan g =1 is position below 1st lantern,
etc.)
Veiling luminance calculation
Veiling luminance is calculated as

where q is the angle between where the eye is looking and the direction of
the location of the lantern. In most lighting standards the following is
used for the calculation,
· Driver
one quarter across the road
· Driver
1.5m high
· Driver
looking down at 10
· First
lantern used in calculation is at 200
· In
the BS it is required to include the contribution from all lanterns within
500m of the observer, however the calculation in any row of lanterns may
be terminated when the contribution of a given lantern is below 2% of the
total.
British Standard requirements
There are two standards used namely,
· BS5489
Part 2 – Traffic Routes
· BS5489
Part 10 – Motorways
The lighting requirements in part 2 are,
|
Category
|
Average Illuminance
|
Overall Uniformity
|
Longitudinal Uniformity
|
Examples
|
|
2/1
|
1.5
|
0.4
|
0.7
|
High speed roads. Dual carriageway roads
|
|
2/2
|
1.0
|
0.4
|
0.5
|
Important rural and urban traffic routes. Radial roads
|
|
2/3
|
0.5
|
0.4
|
0.5
|
Connecting, less important roads. Residential major access roads
|
In addition all roads must have a surround ratio of at least 0.5. TI is
limited to 15% for high speed roads and in rural areas, and 30% in all other
cases.
For motorways the requirements are,
· Luminance
– 2.0 cd/m-2
· Overall
Uniformity – 0.4
· Longitudinal
Uniformity – 0.7
· Threshold
Increment - 10%
· Luminance
on hard shoulder – 0.5 cd/m-2
L06 (6). Glare
Glare Index Calculation(CIBSE pp 172, 200)
The CIBSE glare index system for the evaluation of discomfort glare is described
in CIBSE TM10.
The glare index system can be applied to a wide range of conventional luminaires,
but it does have some limitations. It cannot be applied to large area light
sources such as luminous ceilings, since the basic formula in the invalid. It
cannot be applied to coffered ceilings and similar large cut-off luminaires. Also
it may underestimate the discomfort glare for some ceilings-mounted luminaires,
especially those in which the luminaire intensity distribution is such that
the luminance of ceiling adjacent to the luminaire is greater than the luminance
of the luminaire itself. Glare indices are specified for particular building
types. These are set three apart, since this is the minimum difference being
necessary for a change in discomfort glare sensation to occur.
Basic Glare Index Formula
CIBSE uses the glare formula,

where
· Lb =
Luminance of background as seen by observer
· Lj =
luminance of luminaire j as seen by the observer
· wj =
solid angle of luminaire j as seen by the observer
· pj =
position index of luminaire n as seen by observer
This method normally requires a computer program, but has the advantage
that the formula can be applied to individual, randomly spaced or regular
arrays of luminaires for any specified direction. The second method, calculating
glare indexes based on photometric data provided by the manufacturer, is
sufficiently accurate for most purposes, and is easy to use.
Uncorrected Glare Indices, with correction factors
This method is based upon the following assumptions;
· The
luminaires are at a SHR of 1.0
· The
luminaires are at a height of 2.0m above eye level
· The
total light output of the lamps in the luminaire is 1000 lumens
· the
observer is located at the mid-point of a wall, with horizontal line-of-sight
towards the centre of the opposite wall
· the
eye level is taken as 1.2m above floor level.
Correction terms can be applied to the uncorrected glare index to allow for
change in mounting height and lamp output per luminaire. Currently there
is no correction for other spacing to height ratios.
Uncorrected Glare Indices are tabulated according to room dimensions and
reflectances. We specify the room dimension in terms of multiples of the
mounting height above eye level. The x direction is always perpendicular
to the line of sight, and the y direction is always parallel to the
line of sight. The worst glare conditions will occur for viewing from the
centre of wither the long wall or the short wall. Interchanging x and y will
allow for this. When the glare index has been found (interpolation may be
needed) it must be corrected for
· mounting
height above 1.2m eye level
· total
lamp luminous flux per luminaire if this differs from 1000 lumens
· extra
correction terms if the published UGI table covers a variety of luminaire
sizes or lamp types
These correction terms are added, or subtracted, from the initial glare
index to give the final glare index of the installation. The height correction
and total luminous flux correction may be calculated as follows;
· Height
correction term -
where
H is the height above eye level(m).
· Total
lamp luminous flux correction term -
where F is
the luminous flux per lamp(lumens) and n is the number of lamps per
luminaire
Factors in detemining glare index
· Bare
batten can be acceptable if the surface are high enough reflectance
· Crosswise
viewing increases glare, except for CAT luminaires
· Glare
is worse if ceiling height is lower, as the position index is stronger.
· There
is a lower glare index for louvred fixtures; lower in the transverse angle,
and this is the principal angle of viewing
· Glare
is increased if the wattage of the lamps is increased, also if the number
of lamps increases, since the luminous area increases.
L06 (7). Field Measurement of Light
Illuminance meters
The performance requirements for illuminance meters are set out in BS
667:1996. The standard defines two types of meter,
· Type
L – high accuracy, used for laboratory measurements
· Type
F – some accuracy has been sacrificed in order to make the instruments portable.
The standard considers a number of potential causes for errors, and set
tolerances on them,
· Calibration
uncertainty
· Non-linearity
· Spectral
correction factor
· Intra-red
response
· Ultra-violet
response
· Cosine
correction (unless marked as uncorrected) – It is important that light coming
away at angles away from the norm are given the correct weighting according
to the cosine formula used in the calculation of plane illuminance. This
is checked by illuminating the photometer head with a small source, and then
rotating the head, checking the angle of rotation and noting differences
from expected
· Fatigue
· Temperature
change
· Range
change
A meter which just meets the requirements of this standard would have a
best measurement capability of ±4% (type L) or ±6%
(type F) when used on any of its calibrated ranges.
Luminance meters
Luminance meters have a similar set of errors to illuminance meters,
· Calibration
uncertainty
· Linearity
· Spectral
Correction
· Infra-red
response
· Ultra-violet
response
· Fatigue
· Temperature
change/K
· Directional
Response – Luminance meters should have a uniform response across their designed
field of view
· Effect
from surrounding field – A luminance meter should not respond to light outside
its field of measurement. This can be tested by using a gloss trap which
is slightly larger than acceptance error, and exposing the meter to a large
uniform field of luminance
· Errors
of focus – this may be due to changes in the light transmitting properties
of the optical system of the meter as the focus is changed
· Range
change
A meter which just meets the requirements of this standard would have a
best measurement capability of ±5% (type L) or ±7%
(type F) when used on any of its calibrated ranges.
Interior measurements
Section 5.3 of the CIBSE Code gives guidance on field measurements
or interior lighting. However, since it was published in 1994, it refers
to the previous version of BS 667, published in 1968.
Care needs to be taken not only with measuring the light, but measuring
and noting the conditions at the time of the test. Things that should be
noted are,
· The
state and age of any lighting system
· The
state of daylight
· The
amount of furnishing and people in the space
· The
surface finishes of the room
To measure the average illuminance, it is necessary to measure the lighting
at several places on the working plane. The minimum number of points that
may be measured is dependent on the Room Index,
· Below
1 – 9 points
· 1
-> 2 – 16 points
· 2
-> 3 – 25 points
· 3
and up – 36 points
These values are for SHR of up to 1.5:1. We lay these points out in a regular
array.
Road measurements
With road measurement it is important to ensure there is no shadow caused
by the person taking the reading. With illuminance measurements it is often
to dark to read the display on the meter, so a meter with a hold facility
is a good idea so the meter can be read with the use of a torch.
For luminance measures, the following are important,
· Ensure
the luminance meter is located in the correct observer position
· Measure
and record the geometry of the installation
· Mark
out the grid of points to be measured with moveable markers so that the marker
may be removed with the meter has been aimed, but before the measurement
has been taken
· Check
the supply voltage to the lighting, and not the age and condition of the
lamps
· Note
condition and state of the road surface particularly if it is wet or dry
The meter used should have a 20’ arc of less angle of acceptance in the
horizontal direction and smaller than 2’ arc in the vertical direction.
L06 (8). Design for seeing – Cubic Illuminance
Overview
Cubic Illuminance (Cuttle, LR&T 1997) specifies the spatial distribution
of illuminance about a point in terms of the illuminances of the six faces
of a cube centered at the point. Cuttle proposes it as the basis for a system
of applied photometry. The reasoning underlying this proposal is that procedures
for both predicting and measuring the six cubic illuminances at a point are
practicable. Also, when the cubic illuminance is specified, either by calculation
or measurement, a variety of indices relating to the spatial distribution
of illumination about the point may be readily derived.
The main advantage of cubic illuminance is that it moves illuminating engineering
into the third dimension. It goes beyond horizontal illuminance on the working
plane, and allows for the designer to extract information, e.g.,
· Balance
of illuminance on horizontal & vertical surfaces
· The
spatial distribution of illuminance, and how it affects 3-d objects
· Variation
of illuminance, as viewer position moves
The vector approach
Definition: Cubic illuminance is the specification of the directional
distribution of incident luminous flux at a point in space in terms of pairs
of opposed planar illuminances normal to three mutually perpendicular axes
intersecting at the point. A typical specification of cubic illuminance
comprises six illuminances related to the surfaces of a small cube centered
at the measurement point with the surfaces of the cube aligned in accord
with the principle dimensional axes f the surrounding space.
Vector geometry is used, since it represents a useful shorthand notation
for deal with the three-dimensional aspects of cubic illuminance. We can
consider illuminance to be a vector E, and indeed this concept has
been around since the work of Mehmke(1898). The concept of the illumination
solid aids visualization of the three-dimensional illuminance distribution
around a point. The point may be on the surface of the solid or contained
within it, and the distance in any direction from the point to the surface
of the solid is proportional to the planar illuminance at the point normal
to that direction.
Measurement
Single Cell photometry
The most straightforward was to measure cubic illuminance is to mount a
small solid cube at the measurement point, and to measure successively the
illuminance on each face. Rowlands & Lowe used this technique,
but it is tedious, and difficult to do.
Automatic single cell photometers require rotation of the cell or that a
fixed cell is exposed to all the different directions by a mirror, or switching
fibre optics.
Six-cell photometry
The simplest version consists of six cells mounted on the face of a cube,
and Simons has developed such a device. Refinements such as a laser
to target onto walls and automatic collation of information from a laptop
are possible. The aim is to produce a device that is as easy to use as a
simple photometer, while allowing accurate 3-d information to be gathered.
Calculation
Direct component
We can state the vectorial form of the point source equation,

where
is
the unit vector in the direction of S at the point of interest P,
and
is
the unit vector normal to the plane of the surface at P. To find
the direct component, we sum all the illuminances falling on the plane.
Indirect component
We can determine the inter-reflected component by using radiant flux transfer
theory, or radiosity. Usually this accuracy is not needed, and we
can use the mean room surface illuminance, which is equal to the mean room
surface exitance,

where, FRF is the first reflected flux,
.
Derived measures
The illuminance solid contains a vector component, where on any axis the
component of the illumination vector equals the illuminance difference in
opposite directions. In this way, the vector component represents all the asymmetric components
of the illuminance distribution. The symmetric component is obtained
by subtracting the vector component.
The illuminance of a surface of any orientation at the reference point is
the sum of the illuminances due to the vector and symmetric component. This
is a remarkable finding that illuminance distribution can be examined in
terms of these two components, and it provides the basis for estimating a
variety of indices that relate to characteristics of spatial illumination.
Illuminance equations
Planar Illuminance,

Scalar illuminance,

Hemispherical Illuminance,

Cylindrical Illuminance,

Semi-cylindrical Illuminance,
