L05 – Lighting Practice
1. Overview
2. Lighting Legislation I – Lighting related legislation
European and International Legislation
Current activities in European Standardization (From Lecture 5)
Construction, Design & Management Regulations (CDM)
Building Regulations, Part L
Construction and Safety of fittings (BS 4533)
3. Lighting Legislation II – CIBSE Code
Introduction to the code
Lighting recommendation for specific types of interior and activity
Maintained Illuminance
Modifying factors flowchart
Examples
4. Lighting Legislation III – CIBSE Lighting Guides
Lighting for offices
The industrial Environment
Hospitals and healthcare
Museum and art gallery guide
5. Design and construction issues I – Luminaires
Luminaire design and construction
Luminaire Design
Luminaire Testing
Luminaire Photometry
6. Design and construction issues II – Utilization factors
Calculation of utilization factors
7. Design and construction issues III – Daylight
Designing for daylight
9. Lighting Design in practice I –Lighting Application Studies [gd]
10. Lighting Design II – Designed appearance
11. Lighting Design in practice III – Case Studies
L05(2). Lighting Legislation I – Lighting related legislation
European and International Legislation
There are a wide range of legislation that a practicing lighting designer
needs to be aware of, at the national, European and international level.
Standards bodies
International
· IEC
– responsible for electrical and mechanical safety standards
· ISO
– non-electrical standards e.g. building and ergonomic issues; daylighting
· CIE
– Art & Science of lighting – daylighting, electric lighting, photometry,
colour, photo-biology, vision systems
At the European level, there are bodies that duplicate some of those at
the international level,
· CENELEC « IEC
· CEN « ISO
· CIE
also works at this level
All of these bodies produce standards documents, attempting to harmonize
standards across Europe. An EN standard is an agreed technical text,
which carries with it the strict obligation to be implemented as a national
standard. A HD standard shows technical equivalence throughout Europe
(??).
There are several EC directives that are relevant for lighting related work,
· Workplace –
This is embodied in the Health & Safety 1992 regulations. It
covers,
· Daylight
levels
· Maintenance
issues of glazing systems
· Suitable
and sufficient lux levels in the workplace
· Advises
that as far as possible, natural lighting should be used
· Suitable & sufficient
emergency lighting should be present
· Use
of Work Equipment – this discusses things that are used by people in
the workplace, i.e. luminaires, which are covered by BS4533 – Luminaires. In
summary, it states that luminaires should be safe and healthy
· Display
Screen Equipment – This is covered in Health & Safety DSE 1992. It
states that employers need to do risk assessments for health & safety. It
gives minimum standards for disturbing reflections. It is codified in CIBSE
LG3. This provides limits for luminaire angular cutoff for areas of
constant/ intermittent/ occasional DSE use. This takes into account age
and type of equipment (white on black, or black on white). It states the
main areas that cause problems are
· High
luminance reflections in screen
· Static
imbalance in far field
· Dynamic
imbalance in near field
It is the employers’ responsibility to consider working patterns and to
provide
· Adequate
screen technology
· Mini-breaks
to give visual rest
· Eyesight
tests for employees
· Safety
signs at work – this covers self-illuminated emergency signs
· Machine
safety – localized lighting fitted to machines e.g. lathes. Must provide
independent task illuminance from environment.
· Constructions
products (CE mark) - It is an offence to sell non-conforming equipment
within the EC
· Electromagnetic
compatibility – Luminaires should not suffer interference or interfere
with other equipment
OPUS lists all relevant standards.
Current activities in European Standardization (From Lecture 5)
· Voltage
harmonization
· Pre
1995 – 240V ± 6%
· Jan
1995 – 230V + 10% / - 6%
· By
2003 – 230 ± 10%
· No
change in the supply voltage
· Voltage
harmonization agreed by DTI against wishes of lighting industry who cited
safety problems if no change in supply voltage
· Testing
of Lighting products
· Products
marked 240V – tested at 240V ± 6%
· Products
marked 230V – tested at 230V ± 6%
· UK
input to standards w.r.t. luminaire testig based on ±6%,
so UK had better safety than ±10% countries. Importing 230V tested products
can therefore give problems
· All
UK products now to be marked 230V
· GLS
Lamps
· 230V
lamps on 240V
· life
reduced from 1000 hr to 560 hr
· temperature
increase of 5%
· increase
in accidents while chaging lamps
· increased
fire risk
· Standard
GLS lamps cause the worst problems if 230V lamps used on 240V supply
· Increase
in accident rate
· Market
penetration 1% - Deaths 0, Hospital treated injuries 26, fire brigade call-outs
6
· Market
penetration 15% - Deaths 1, Hospital treated injuries 400, fire brigade call-outs
100
· Based
on ERA study
Construction, Design & Management Regulations (CDM)
The CDM regulations plan, design and manage health and safety at
construction and post-construction stage. It covers all design work, and
all construction work which last for over 30 days.
Principal Parties
The main parties in CDM are
· Client
· Designer
· Principal
Contractor(s)
· Self
Employed Contractors
· Planning
Supervisor
Each must do two things,
· Health & Safety Plan –
This takes input from the designer and contractor
· Health & Safety File –
This consists of a logbook which is handed over to the client. It contains
all the risk assessments and procedures developed during the build process.
The client appoints Planning Supervisor who
· Controls
designer, re. Health & Safety
· Responsible
for creating plan and file
· Seeks
info from contractor ( what was built)
The responsibilities of the designer include
· Site
analysis to identify main hazards during construction, maintenance and disposal
e.g. mercury lamps
· Where
you can avoid hazards, come up with a ‘method statement’ in the form of a
procedure which then goes into the logbook.
The designer may need to have chartered status, or be supervised by one.
Building Regulations, Part L
Part L is concerned with the conservation of Fuel & Power. It
states that a scheme must be designed and constructed to use no more than
reasonable power and fuel. It also must provide provision for reasonable
control. This applies to new build and change of use.
There are two ways to comply with part L,
· Either
95% of installed lighting circuit watts of lamp types listed
· SON
· MK
· Induction
· Tubular
Fluorescent (25mm diameter with HF ballast only)
· Compact
Fluorescent (all ratings > 11W)
OR
· The
lighting designer must demonstrate that the average efficacy of the installation > 50
lumens per circuit watt
Exemptions are given in certain cases – Exterior, Display, Domestic, Emergency
Lighting. Judgement is required in Churches, Cinemas, and other low use
buildings. If you work to the CIBSE Code recommendations, you will satisfy
Part L.
Construction and Safety of fittings (BS 4533)
There is an agreed international document for Luminaire specification produced
by the IEC, IEC 598 Luminaires. This provides much of the basis for
the British Standard BS4533 Luminaires. The corresponding European Standard
is EN60 598-1.
The main functions of the luminaire are:
· To
redirect light from the bare lamp in the preferred direction with the minimum
of loss
· To
reduce glare from the source
· To
be acceptable or contributory in appearance
Other important aspects are,
· Lamp
Protection – The lamp must be mechanically supported and protected
· Electrical
safety – The lampholder, control gear and associated wiring must be protected
and supported
· Heat
dissipation – Heat from the lamps and control gear must be conducted away
from heat-sensitive parts and surfaces near the luminaire
It is unlawful to make, or hold in stock, or
offer for sale any electrical apparatus that is unsafe. With regard to luminaires,
BS4533 is accepted by HM Government as a “safety” specification. Manufacturers
can give assurance that luminaires are safe by marking them with the BSI
safety mark.
Luminaire Markings
Certain information is required by BS4533 to
be marked onto luminaires,
· Mark
of Origin
· Rated
Voltage(V) (For GLS, no mark unless different from 250V)
· Rated
max ambient temp, if other than 250C
· Class
of luminaire
· 0
– luminaire relies on basic illumination (not permitted in UK)
· I
– Functional insulation throughout with earthing terminal or earthing cable
and plug
· II
- Double and/or reinforced insulation
· III
- luminaire protects against electric shock by running on a supply at safety
extra low voltage (< 50V)
· IP
number (ingress against foreign bodies/ingress against moisture)
· Makers
model number
· Rated
wattage(W) of the lamps
· Classification
of the material of the supporting surface
· Non-combustible/
no ballast, flammable surface/ ballast, flammable surface
· Information
concerning special lamps
· Symbol,
where luminaires use lamps similar in shape to ‘coolbeam’, where this might
impair safety
· Terminations
should be clearly marked earth and live
· Minimum
distance of spotlight from lit objects
Luminaire characteristics (CIBSE pp. 75-83)
1. Mounting
position – recessed, surface, pendant
2. Polar
curve
3. SHR
NOM
4. Utilization
factor
5. Glare
index
6. Room
surface brightness
L05 (3). Lighting Legislation II – CIBSE Code
The CIBSE Code for Interior Lighting is aimed at
a) Specifying
the lighting conditions appropriate for a wide range of interiors
b) Offering
guidance on design methods for obtaining those conditions
It is organized in six parts,
Part 1.This summarizes the effect of lighting conditions on
the performance of tasks, the appearance of the interior and the comfort
of the occupants
Part 2.Recommendations of maintained illuminance and other
design criteria, both specific and general, which are suitable for a large
number of interior and exterior applications
Part 3.Describes the properties of interior lighting equipment
which is generally available
Part 4.Sets out suitable design procedures
Part 5.Appendices
Part 6.Glossary, Bibliography and references
Recommendations for daylight
In most types of buildings, users prefer rooms to have a daylit appearance
during daytime hours. This appearance can be achieved, even if there is
a significant amount of daytime electric lighting by ensuring that changing
brightness of daylight is clearly noticeable of walls and other interior
surfaces. It is also necessary to achieve sufficiently bright interior surfaces
to avoid glare from contrast with the sky.
Daylight for general room lighting
· If
daylight is not normally used during daytime hours, the average daylight
factor should be not less than 5%. The internal reflections and positions of windows
should be such that the inter-reflected light is strong and even. When the
shape of the room causes the daylight distribution to be uneven, supplemental
electric lighting may be required.
· If
daylight is to be used during daytime the average daylight factor should
not be less than 2%. In a room with less than 2% average daylight factor, the appearance
will be that of an electrically lit interior.
· When
daylight alone provides the task illumination, the illuminance should not
fall below that given in the specific recommendations for the interior type. The
uniformity within the immediate task area should be similar to that provided
by electric lighting although there may be variation in daylight in different
part of the interior.
· When
there is a significant amount of daylight, electric lighting may be needed
to reduce the contrast between internal surfaces and the exterior view. It needs to fall on the walls and other surroundings
of the window opening. The brighter the view, the higher the required surrounding
luminance.
· If
electric lighting is required to increase the illuminance in areas distant
from the window, the average working plane illuminance due to electric lighting
should not be less than 300 lux. If lower levels are used there may be noticeable
contrast between areas near windows and other parts of the room, causing
an impression of gloominess or harshness.
· In
general room lighting, apparent discrepancies between the colour of electric
lighting and daylight can be reduced by using lamps of intermediate colour
temperature (3300-5300K) and screening lamps from the view of the occupants, using opaque louvres
rather than translucent diffusers.
General recommendations for electric lighting
These recommendations form the foundation for the specifications and design
of all electric lighting to ensure visual comfort and satisfaction.
Illuminance
The recommendations given for specific applications are consistent with
the rule that working spaces, which are to be occupied for long periods,
should have a maintained illuminance of not less than 200 lux on the working
plane. We assume the people who are working have normal vision. If
a significant number of people occupying the space have some degree of
visula impairment, the maintained illumnance could be increased. The recommendations
generally assume a viewer age of 40-50 years.
Illuminance Variation
For the task area, and the immediate surround, uniformity is important. If
the precise size of the task area is not known, calculations can be based
on an area measuring 0.5m x 0.5m located immediately in front of the observer
at the edge of the desk or working surface.
It is recommended that the uniformity of illuminance (minimum to average
illuminance) over any task area and immediate surround should not be less
than 0.8.
We must try and avoid excessive variation
of horizontal illuminance across the space: the diversity of illuminance
expressed as the ratio of the maximum illuminance to the minimum illuminance
at any point in the ‘core area’ must not exceed 5:1. The
core area is that area of the working plane having a boundary 0.5m from
the walls. Installations lit by ceiling-mounted arrays designed by the
‘lumen method’ following the usual layout and spacing criteria will normally
satisfy the uniformity requirements.
In a localized or local lighting scheme, the normal design method is to
establish the highest recommended task illuminance, and then to set the ‘ambient’
level at one thrid of this value or to the requirement of the non-task areas
(whichever is greater). The illuminance at the task is then ‘topped up’
with localized or local lighting to the apropriate task level.
Luminance and illuminance ratios
Luminance differences may be specified or measured in terms of the ratio
between one luminance and another. Suggested targets are task-to-immediate
surround 3:1, and task-to-general background 10:1.
Ceilings
The recommendation for general lighting with a predominantly
downward distribution is for the ratio of average illuminance on the ceiling
to the average illuminance on the horizontal working plane to be within the
range 0.3 to 0.9.
In general the ceiling cavity reflectance should be as
high as possible, at least 0.6.
For indirect lighting, the average luminance of all surfaces forming
the ceiling cavity should be not more than 500 cd/m2. However
small areas of luminance up to 1500 cd/m2 will generally be
acceptable, provided sharp changes from low to high luminance are avoided.
Walls
Higher reflectance of wall and partition surfaces will increase the perception
of lightness in the interior. Walls with windows are a particular case. The
walls surrounding a window should have a reflectance not less than 0.6 in
order to reduce contrast.
The ratio of the average illuminance on the walls to the average illuminance
on the horizontal working plane is related to the average vertical plane
illuminance throughout the space. This has been shown to give good correlation
with visual satisfaction for office lighting. The recommendation is for
the ratio of the average illuminance on any wall or major partition surfaces
to the average illuminance on the horizontal working plane to be within the
range 0.5 to 0.8.
In general the effective reflectance of the principal walls should be
between 0.3 and 0.7.
Floor and working plane
The reflectance of the floor cavity plays an important part in visual appearance
of a room. With most lighting installations a proportion of the light on
the ceiling will have been reflected off the floor. Low reflectance bench
and desk tops should be avioded since these surfaces have a major effect
on effective floor cavity reflectance.
In general it is undesirable for the average floor cavity
reflectance to exceed 0.40 or fall below 0.20. The reflectance of the area
surrounding the task should not be less than one third of the task itself. In
the case of office tasks involving white paper this will require desk tops
to have a reflectance of at least 0.30.
Colour appearance
Some general rules to help with the selection of lamp source colour are,
· For
rooms lit to an illumination of 300 lux or less, a warm or intermediate colour
temperature is preferred; cold apparent colour lamps tending to give rooms
a gloomy appearance at lower illuminances
· Where
it is desirable to blend with daylight, intermediate CCT sources should be
used
· Different
colour lamps should not be haphazardly used in the same room
Colour rendering
Where work involving accurate colour judgement is required, electric light
sources with high CIE colour rendering indices (Groups 1A or 1B) should be
used. In general, light sources with good colour rendering properties (Group
1B) make objects appear more colourful than do those with medium colour rendering
properties (Group 2, 3 and 4).
Modelling & Emphasis
Illumination which falls on an object from all directions, enables the object
to be seen, but does not reveal much of the form or texture because there
are few, if any shadows. The relationship between the intensity of the directional
lighting and the diffuse component is known as the vector/scalar ratio. A
vector/scalar ratio of 1.2 to 1.8 will prove satisfactory in normal general
lighting conditions where perception of faces is important. Under such conditions
facial modelling will usually appear balanced and natural.
Display lighting tends to call for greater impact and emphasis. The Display
Iluminance Ratio (DIR) is that between the general horizontal plane
illuminance and the value of local illuminance in the plane of the object
to be displayed. Greater degrees of emphasis are likely to require lower
vaues of general diffused lighting to avoid the need for excessive values
of local display illuminance.
Energy efficiency
Energy efficiency can be achieved in two ways
· By
using the most efficient lighting equipment
· By
using effective controls so that lighting is not in use when it is not needed
The recommendations state that an average initial circuit luminous efficacy
of at least 65 lm/W for the fixed lighting equipment should be achieved.
Recommendations for specific types of interior and activity
These provide
· Quantitative
guidance on the maintained illuminance, and limiting glare index for a wide
range of interiors and/or activities.
· Qualititative
advice on the aspects of the interior/activity which should influence the
selection of lighting equipment and design of the lighting installation
· Notification
of statutory and advisory documents relevant to each interior/activity
Maintained Illuminance
The maintained illuminance, Em, is the average illuminance
over the reference surface at the time maintenance has to be carried out
by replacing lamps and/or cleaning the equipment and room surfaces.
The Design Maintained Illuminance is the illuminance to which the interior
should be lit after modifying factors have been taken into account departures
from the assumed typical conditions,
· The
visual demands of the task
· The
duration of the work
· The
consequences of any erros
· Energy
considerations
5. Design and construction issues I – Luminaires
Luminaire design and construction
In ‘Design for the Real World’, V. Papanek describes a product design
methodology which balances practical considerations with aesthetic ones.
We can apply these criteria to the design of a luminaire by asking the following
questions,
· Need
– Do we need a new it?
· Use
– How is it to be used?
· Aesthetics
– Is it beautiful?
· Materials,
Tools, Processes – How do they interact?
· Telesis
– Which culture gave rise to it?
· Association
– What does it remind you of?
Luminaire Design
The function of the luminaire is:
· To
redirect light from the bare lamp in the preferred direction with the minimum
of loss
· To
reduce glare from the source
· To
be acceptable or contributory in appearance
Other important aspects are,
· Lamp
Protection – The lamp must be mechanically supported and protected
· Electrical
safety – The lampholder, control gear and associated wiring must be protected
and supported
· Heat
dissipation – Heat from the lamps and control gear must be conducted away
from heat-sensitive parts and surfaces near the luminaire
· Finishing
– Attention must be paid to the protection of the luminaire finish to corrosion
and degradation
· Maintenance
– Ease of cleaning and relamping
As a luminaire designer, one must appreciate the range of materials and
surface finishes it is possible to use in a luminaire,
· Metals
· Ferrous
– sheet steel
· Non-ferrous
– Aluminium alloys
· Finishes
· Stove
enameling
· Electrostatic
spraying
· Dry
powder spraying
· Plastics
· Thermoplastic
- Polystyrene, Acrylic, Polycarbonate, PVC, ABS, Nylon, PBT, Polypropylene
· Thermosetting
– Urea/Phenolic, GRP
These all have different properties,
Material
|
Melt Point (oC)
|
Operating Temp(0C)
|
Flammability
|
|
Nylon 66
|
260
|
-
|
Self extinguish
|
|
Acrylic
|
160-180
|
-
|
Flammable
|
|
General Purpose PVC
|
-
|
70
|
Unstressed
|
|
High Temp PVC
|
-
|
105
|
|
|
High Temp EVA
|
-
|
140
|
|
|
Silicone Rubber
|
-
|
200
|
|
|
PTFE
|
-
|
260
|
|
|
Polycarbonate
|
-
|
-90 -> +135
|
-
|
Reflectors
Material
|
Regular r
|
|
Al Commercial grade
|
70
|
|
Al Super purity
|
80
|
|
Aluminised Plastic
|
94
|
|
White paint on steel
|
5 (diffuse 75)
|
Diffusers
|
Material (all 3mm)
|
Transmittance (%)
|
|
Flint glass
|
92
|
|
Clear Acrylic
|
92
|
|
Opal Acrylic
|
50 - 80
|
|
Polystyrene
|
92
|
|
Polycarbonate
|
88
|
Luminaire Testing
Electrical Safety
· Test
finger – no live parts touched accidentally
· Check
creepage and clearance distances
· Insulation
resistance
· Electric
strength – high voltage flash test
Mechanical Safety
· Fixing
and suspension must be sufficiently strong to withstand overload conditions
· Nut
and screw fixings tested using torque tools
· Corrosion
testing in saline atmospheres
· Impact
testing by impact hammer ( or large prison officers )
Thermal Safety
· Temperature
endurance tests – Subject the luminaire to on/off switching cycles for seven
days in ambient temperature, +10 degrees above ambient and at over voltage
· Temperate
tests take place in draught free enclosures using thermocouples placed at
relevant positions with luminaires operating at 110% voltage.
· No
point on external surface should be hot enough to burn in normal use
· Components
should be heat resistance – each given a max operating temperature
· Mounting
position is important – distance from adjacent surfaces?
Other factors are important,
· Marking
of luminaires
· Ease
of maintenance
· Catches
and enclosures of fittings
· Ease
of cleaning
· Ease
of relamping
Luminaire Photometry
BS 5225 gives details of measurement techniques for obtaining photometric
data for luminaires, including laboratory conditions, and procedures for
simple luminance and illuminance measures.
A goniophotometer is used to measure the intensity distribution of
a luminaire. It uses a photocell which has a spectral sensitivity which
corresponds to the V(l) curve. We use calibrated lamps, which have been run for 100 hours
to allow them time to stabilize.
Certain characteristics are required for the goniophotometer to produce
accurate results,
· Minimize
stray light by light baffles
· Control
air temperature
· Avoid
errors due to
· Non-linear
photocell
· Voltage
fluctuations
· Mirror
sagging
· Mirror
reflectance
The goniophotometer maintains the luminaire in the desired attitude. You
measure in the position of luminaire use. To achieve the desired optical
path length, mirrors are often used; the path should be at least five times
the largest dimension of the light fitting. The mirrors should be optically
flat, and have a uniform surface finish.
Readings are taken in the azimuth and altitude of the luminaire. In a luminaire
that is nominally symmetrical, azimuthal readings are taken every 400. For
all other luminaires, including asymmetrical luminaires, readings are taken
every 300. In altitude, readings are taken every 100,
in the centre of the spacing e.g. 5,15,25… If the luminaire is light concentrating,
take measurements every 50.
6. Design and construction issues II – Utilization factors
CIBSE TM5 – Calculation & Use of utilization factors (1980) is
concerned with the production of taking raw photometric data in terms of
uncalibrated intensity distributions of luminaires and converting that into
information which can be utilized directly in lighting calculations, in the
form of utilization factor tables.
Certain assumptions are made in TM5,
· Rooms
are square (rectangular rooms of same room index are fine, provided L:W < 4:1)
· Room
surfaces are uniformly diffuse
· Luminaires
are in square array with half-spacing to perimeter
A non-rectangular room can be broken down into a series of adjoining squares
rooms.
OCalculation of utilization factors
The procedure can be broken down into a series of discrete steps, each of
which TM5 provides a worksheet for,
· Calibrate
of raw photometric data
· Determine
spacing of luminaires on which to base the UF table
· Calculate
proportion of bare lamp flux received directly by surfaces of room for each
Room Index
· Find
the contribution from inter-reflected light for each set of room reflectances
The calculation of Zonal Flux and Light Output Ratio (Worksheets 1a & 1b)
We assume that the luminaire has been photometrically tested in accordance
with BS5225: Part I. A table of intensities will be available from this
measurement. For symmetric luminaires (usually incandescent), we require
azimuth readings every 450. For all other luminaries, we require
readings every 300.
In order to calculate Zonal Flux, e only need readings at 50,150,250,
etc. Values at 100, 200, … 900 are required
for drawing polar curves, and calculating uniformity.
The results of this worksheet are,
· Scale
Factor ( ratio by which uncalibrated results must be multiplied to calibrate
them per 1000 lamp lumens)
· ULOR,
DLOR and LOR
· Calibrated
axial and transverse intensity distributions
· Zonal
flux ( i.e. amount of lamp flux falling in each 100 axial band
in all directions from the luminaire
The selection of Spacing to Mounting Height Ratio
The uniformity ratio is defined as the minimum to average illuminance
over the task area. The code recommends this should not be less than 0.8. The
UF tables should be based on a spacing to height ratio (SHR) close
to the maximum spacing to mounting height ratio at which this uniformity
is achieved. This will enable the most economical lighting installation
to be planned. In practice, the spacing may be closer to avoid shadowing
or to increase the illumination.
Two simplifications are made for the purposes of the calculation,
· A
standard layout of 16 luminaires is adopted
· The
effects of inter-reflected light are ignored
The first simplification has little effect since adding more luminaires
only marginally affects the illuminance at the centre. The second simplification
tends to slightly underestimate the uniformity that will be achieved, since
inter-reflected light is more evenly spread than direct light.
A uniformity of 0.8 is normally achieved over the central region if the
ratio of the minimum to maximum illuminance is greater than 0.7.
Two spacing to height ratios are calculated,
· SHR
MAX – the widest spacing at which a ratio of minimum to maximum illuminance
greater than 0.7 is achieved
· SHR
NOM – the greatest value of SHR in the preferred series 0.25, 0.5, 0.75,
etc. that will achieve this criterion. Utilization factors are based on
this value.
Distribution Factors
The distribution factor is defined as the fraction of bare lamp flux
that reaches the reference surface directly (without inter-reflections). For
the purpose of the calculation, the room is considered to consist of only
three surfaces, the horizontal reference plane, the luminaire plane and the
walls in between these two.

The space above the luminaires (for suspended luminaires) and the space
below the horizontal reference plane are designated the ceiling cavity and
the floor cavity respectively.
The distribution factor DF(F) for the floor cavity is the proportion
of bare lamp flux that reaches the floor cavity directly. Similarly for DF(C) and DF(W). To
calculate the distribution factors, we use the zonal multipliers, which give
the fraction of flux in each 100 band.
Utilization Factors
We now have the amount of flux reaching the surfaces directly. Now we calculate
the inter-reflected component by using transfer factors. The Transfer
factor TF(S1,S2) from one surface S1 to another surface S2 is
the ratio of the total flux falling on S2 as a result of the flux illuminating
S1, to the direct flux on surface S1. The Transfer factors from the ceiling,
walls and floor onto the reference surface for a range of room indices and
surface reflectance are given in TM5. The Utilization Factor UF(F) is
given as follows

There is a standard form for the publication of utilization factor data,
which is shown overleaf.
